DATA FIELD DESCRIPTIONS
For instruction purposes, messages are divided into a number of data fields. By identifying data fields, each
section of the message is more easily defined.
The following data fields and corresponding ASCII character values are utilized in BIC-II messages.
SOM (Start Of Message)
This field contains the Host/BIC-II start of message character.
ASCII character = STX (normally generated by simultaneously pressing Ctrl B on a keyboard)
BIC-II I.D.
This field identifies which BIC-II the message is associated with. Refer to Start Up\Hardware Set Up\
BIC-II I.D.#.
ASCII values = 1 to 8
POINT
Identifies the scan point of the Milltronics product to which the message applies.
ASCII values = 000 to 099
MT (Message Type)
Identifies the type of message, the data pertains to.
Refer to BIC-II Messages and Product Messages for the message types available.
EOM
This field contains the host/BIC-II end of message character.
ASCII character = CR (normally generated by simultaneously pressing Ctrl M on a keyboard)
SOFTWARE SET UP
The BIC-II (in BIC mode) is factory set for communication with a Milltronics AiRanger level measurement
product, with full Format messages, and no Delimiters. If this set up is acceptable, no further set up is
required.
If an alternate set up is required, software set up messages must be transmitted from the host to the BIC-II
before Product Messages may be transmitted to (or received from) the BIC-II. (Refer to BIC-II MESSAGES/
Reset, Delimiters, Format, and Product Mode).
Upon power up, the BIC-II automatically resets the software set up to the factory setting.
PL-371 7 – 2