WIRING FORMATS (cont’d)
BIC-II / AiRanger IV Interconnection
1. BIC-II, ports 1-6, Rx input is non-polarized.
2. Refer to instruction manual PL-250 for wiring of AiRanger IV.
3. BIC-II interconnecting cable shield should be grounded at AiRanger IV only. Insulate shields
at junctions to prevent inadvertent grounding. Use Belden cable 9552, 2 pair shielded,
18 AWG or equivalent. Maximum communication loop length is 3000 m ( 10,000 ft ).
4. All wiring, whether in non-hazardous (as shown) or hazardous areas, must be done in conjunction with
approved conduit, boxes and fittings, and to procedures in accordance with all governing regulations.
5. Set BIC-II and AiRanger IV voltage selection jumpers for proper voltage supply.
Supply voltages higher than voltage selected will severely damage unit.
FIG. 3C
S
mA
TRANSMIT
TB2
TB3 TB1
12
1
2
3
4
5
6
7
8
9
10
1111
10
9
8
7
6
5
4
3
2
1
12
+
GR
+
+
+
BLK
WHT
GR
POWER
RECEIVE
OUTPUT
TEMP.
SENSOR
HOT
SHLD
RC2
RC1
PORT 1
302928272625242322212019181716151413121110987654321
TB1
+
Rx
+
Tx Tx
+
Rx
+
Tx
+
Rx
+
Tx
+
Rx
+
Tx
+
Rx
+
Tx
+
Rx
+
PORT 2
PORT 3
PORT 4 PORT 5 PORT6
H
I
G
H
L
O
W
A
L
A
R
M
Board B
BIC-II
AiRanger IV #1
Terminal Board
to other products
as required
PL-371 12 – 5